Flexible Conduit Adapter Kit
Installation Guide
68-1322-01 Rev. C
06 10
The Flexible Conduit Adapter Kit provides a convenient means to replace the IEC power cord of the Extron PS 124 12 VDC,
4 A power supply (part #60-1022-01), the XPA 1002 (part #60-899-01), or the XPA 2001 (part #60-850-01 and -11) power
amplifier with conduit, where required by local codes.
The Flexible Conduit Adapter Kit includes the following parts:
One EMT adaptor plate
One 6' long electrical conduit
Three 7.5' 14-gauge power wires with spade connectors
One UL rated zip tie wrap
Three auxiliary crimp style spade connectors designed for 14- to 16-gauge wires
WARNINGS: The circuit breaker used for this connection should be rated no less than 15 amps when 14 gauge power
wire is used, or 20 amps when 12 gauge wire is used.
This unit must be installed in accordance with the National Electrical Code and with all local codes.
An ALL-POLE MAINS SWITCH with a contact separation of at least 3 mm in each pole must be incorporated
in the electrical installation of the building. The installation must be carried out in accordance with all
applicable installation rules.
Installation and service must be performed by a qualified electrician only.
CAUTIONS: Make sure that the XPA amplifier or the PS 124 power supply and its attached source device, as well as all
output devices, are turned off and disconnected from the power source before you begin.
A UL listed electrical distribution box is recommended for the termination of the conduit opposite the
PS 124 power supply or the XPA amplifier. See “UL Requirements,” below.
NOTE: Extron recommends using a UL-rated crimp tool to terminate the spade connectors, if this is needed. One
recommended choice is the Molex crimp tool (Molex part #19285-0008).
UL Requirements
The Underwriters Laboratories (UL) requirements listed below pertain to the installation of the flexible conduit onto a
PS 124 power supply, an XPA 1002, or an XPA 2001.
This unit must not be used beyond its rated voltage range.
This unit must be wired to a UL listed distribution box.
NOTE: The UL approved electrical distribution box is not included with the XPA amplifier, the PS 124 power supply,
or the Flexible Conduit Adapter Kit; the installer is responsible for obtaining and installing the distribution
box.
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Installation Guide

Flexible Conduit Adapter Kit Installation Guide68-1322-01 Rev. C06 10The Flexible Conduit Adapter Kit provides a convenient means to replace the IEC

Page 2 - CAUTION:

Flexible Conduit Adapter Kit Installation Guide (Continued)2Installing the Flexible Conduit Cable on a PS 124Install the flexible conduit cable assembl

Page 3 - XPA 1002

310. Slide the conduit nut over the bundle of wires exiting the conduit and onto the conduit itself inside the PS 124. Hand-tighten the nut. (See figur

Page 4 - 100-240V 1.3A

Flexible Conduit Adapter Kit Installation Guide (Continued)443. Remove the two screws holding the hot (brown) wire and the neutral (blue) wire from t